Could you provide an error code meaning for model MSR 5KVA. It show E07 and E8 on display.
Fault code
E-8
Protection Function
6 low voltage
Monitoring point
“1,input voltage
2,output voltage”
condition
output voltage<176v,continued 3s
Phenomenon after protection
Relay cut-off output
When the input voltage>118v or output voltage > 198v, the output will be restored
Within 30s, 3 times of low voltage continuously Relay cut-off output,Program locked.
Restore output after protection
Manual recovery required
Fault code : E7
Protection Function : 9 over load current
Monitoring point :
1,input voltage
2,Current sensor
3,Temperature sensor”
condition
“current reachs 1~1.2 times continue(3600s/temperature coefficient)”
“current reachs 1.2~1.4 times continue(600s/temperature coefficient)”
“current reachs 1.4~1.6 times continue(60s/temperature coefficient)”
current reachs 1.6~2 times continue(30s/temperature coefficient)
Phenomenon after protection
Relay cut-off output,after beeps.
condition
current reachs 2~3 times continue 2s Relay cut-off input,after 2 beeps.
current over 3 times
Phenomenon after protection
Relay cut-off input
Restore output after protection
Manual recovery required